Insulation Monitoring - Setup Instructions
Mosa Power Generators 12054HZDT / 13054HBS
This professional guide describes the correct setup of insulation monitoring (Dossena) for maximum operational safety with minimal false alarms.
🎯 Optimal Settings
For maximum tolerance with safe operation:
| Parameter | Setting Value | Controller Position | Purpose |
|---|---|---|---|
| Pre-Alarm (Pre-AL.) | 50 KΩ | 50 | Early warning without shutdown |
| Alarm (AL.) | 20 KΩ | 20 | Critical alarm with shutdown |
| Operating Mode | N.E./Aut. | N.E./Aut. | IT network, automatic operation |
📄 Complete Instructions
⚠️ Safety Instructions
- All work must only be performed by qualified electrical personnel
- Disconnect and secure the system before maintenance work
- Use appropriate personal protective equipment
- Contact GREMAC Service if in doubt
📞 Support
For questions about insulation monitoring, contact our service:
- Phone: +49 9073 4039870
- WhatsApp: +49 9073 4039870